| PARAMETERS | SPECIFICATION |
| Type | Static Stabilizer (DLSS) |
| Frequency | 47 - 53 Hz |
| Voltage Range | 300 - 525 V or 340 - 480 V AC 3 Phase 4 Wire |
| Proctection MCB / MCCB | 32A - 160A |
| Voltage | 415 V AC |
| Voltage Regulation | +/- 1% |
| Correction Speed | 1000 V/sec |
| Output Waveform Distortion | NIL |
| Effect of Power Factor | NIL |
| Maximum Output Current | 14 A - 105 A |
| Duty Cycle | 100% Continuous |
| Overload | 120% per 1 Minute |
| Efficiency | 97% (Full Load) |
| Protection | |
| Short Circuit | Available |
| Input Over Voltage | 300 V +/- 1% or 340 V +/- 1% |
| Input Under Voltage | 525 V +/- 1% or 480 V +/- 1% |
| Output Over Voltage | 415 V + 5% |
| Output Under Voltage | 415 V - 5% |
| Output waveform | True reproduction of input |
| Over Load | Electronic Over Load Trip with Time Delay |
| Single Phase Prevention | Available |
| Phase Reversal | Available |
| Display | |
| LCD Display | 20*4 LCD Display |
| Voltage | Input & Output Voltage - 1 Phase & 3 Phase |
| Current & Frequency | Output Current - 3 Phase & Frequency |
| LCD Visual Annunciation | Input & Output Over Voltage & Under Voltage, Over Load, Phase Reversal, Error Log |
| Indication & Key Function | |
| Input Normal | Green LED |
| Output Normal | Green LED |
| Phase Fault | Red LED |
| Over Load | Red LED |
| Menu Key | To View Parameter |
| Start Key | To Switch ON Output Load |
| Stop Key | To Switch OFF Output Load |
| Log Key | To view ERROR Log |
| Environmental | |
| Ambient Temperature | 0 - 45 Deg C |
| Humidity | 0 - 90 (RH- Non Condensing) |
| Ingress Protection | IP - 20 |
| Cooling Method | Force Air Cooled |
| Mounting | Castor Wheels with Two Sides Brake |
| Color | Door & Frames RAL 9005 / Front Door RAL 7044 |